technical information
Dimensions
Parameters Unit WGJ-g DUOSOL 200 WGJ-g DUOSOL 250
D mm 600 640
H mm 1440 1430
E mm 1205 1180
F mm 1115 1090
A mm 235 245
B mm 325 335
R mm 325 365
Muff ZW - supply of cold water   ¾" ¾"
Muff CW - supply of hot water   ¾" ¾"
Muff WE - inlet hot water boiler   1" 1"
Muff WY - water outlet of the boiler   1" 1"
Coil connector  KW   1" 1"
Muff circulation  MC   ½" ½"
Muff heater  MG   1 ½" 1 ½"
Connector heater KG   1 ½" 1 ½"
Tube thermometer RK mm Ø12 Ø12
Cork anode AN   2" 2"
Magnesium Anode   Ø 40 x 240 Ø 40 x 240
Thermal isolation   about 50 mm polystyrene foam
The weight of heater without water kg 90 98

 

Technical parameters
Parameter Unit WGJ-g DUOSOL 200 WGJ-g DUOSOL 250
Actual heater capacity dm³ 193 246
Sheathed exchanger Heat exchanger area 1,33 1,42
Capacity exchanger dm³ 19,3 20,5
 
Efficiency hot water

80/10/45°C

70/10/45°C

60/10/45°C

dm³/h

 

960

815

555

 

1020

870

590

 
Constant heating power

80/10/45°C

70/10/45°C

60/10/45°C

 

kW

40

31

22

43

33

23

Heating water flow m³/h 2,3 2,6
Loss of pressure
bar 26 26
Coil The exchange surface of the coil 0,82 0,96
The capacity of the coil dm³ 4,7 5,5
Efficiency hot water

80/10/45°C

70/10/45°C

60/10/45°C
dm³/h

 

610

488

360

 

700

565

415

Constant heating power

80/10/45°C

70/10/45°C

60/10/45°C
kW

 

25,5

20,3

15,0

 

29,1

23,5

17,3

Heating water flow m³/h 1,6 1,9
Loss of pressure
mbar 35 35
ErP Efficiency Class*   C C
Operating parameters water tank
  max. pressure and operating temperature pr = 0,6 MPa tr = 80°C
The parameters of the heating medium in the exchanger jacketed   max. pressure and operating temperature pr = 0,3 MPa tr = 100°C
The parameters of the heating medium in the coil   max. pressure and operating temperature pr = 0,6 MPa tr = 100°C
Thermal isolation   about 50 mm polystyrene foam

* in accordance with applicable since 26 September 2015. EU Commission Regulation No. 812/2013

 

 