EKO-KWRW: 100, 150, 200
characteristics
KWRW 100-200 boilers are hot water boilers, low temperature, automatically controlled, equipped with an aeration of the fuel stack. The boiler is designed for burning fine hard coal loaded manually into the combustion chamber. The boiler construction is made of steel with a thickness of 6 mm for the exchanger and 5 mm for a water jacket.
Basic fuel: fine coal and eco pea coal.
The boiler is equipped with driver EL880 zPID
Available model:
Model | Catalog number | EAN |
EKO-KWRW 100 | 412-10-100 | 5903538243091 |
EKO-KWRW 150 | 412-15-100 | 5903538243107 |
EKO-KWRW 200 | 412-20-100 | 5903538243114 |
technical information
Parameter | Unit | EKO-KWRW 100 | EKO-KWRW 150 | EKO-KWRW 200 |
Nominal power | kW | 100 | 150 | 200 |
The range of thermal power | kW | 30÷105 | 45÷150 | 60÷200 |
Boiler class | 3 | |||
Thermal efficiency | % | 80 | ||
Maximum allowable working pressure | bar | 2,5 | ||
Required flue gas draft | Pa | 37÷57 | ||
Max. temp. of heating medium | °C | 80-85 | ||
Power supply of the fan and driver | 230V/50Hz | |||
Power consumption | W | about 170 | ||
Water capacity | dm³ | 395 | 495 | 650 |
Fuel type (base fuel) | fine coal | |||
Weight without water | kg | 1320 | 1600 | 2400 |
The size of the loading opening | mm | 320 x 500 | 320 x 500 | 320 x 500 |
Depth of furnace | mm | 680 | 830 | 935 |
Width of furnace | mm | 805 | 805 | 850 |
The capacity of the loading chamber | dm³ | 300 | 465 | 670 |
The required minimum chimney section | m² | 0,11 | ||
Dimensions of smoke conduit (height x width) | mm | 300 x 330 | 300 x 330 | 350 x 350 |
Water connections | DN 65; PN 6 | DN 80; PN 6 | DN 100; PN 6 |
EKO-KWRW | A | B | C | D | E | F | G | H | I | J | K | L | M |
100 | 1980 | 1030 | 1120 | 1320 | 1630 | 300 | 330 | 1520 | 1065 | 1005 | 310 | 1450 | 225 |
150 | 2190 | 1035 | 1120 | 1450 | 1825 | 300 | 330 | 1700 | 1170 | 1120 | 310 | 1650 | 225 |
200 | 2450 | 1080 | 1165 | 1655 | 1995 | 350 | 350 | 1915 | 1350 | 1260 | 320 | 1830 | 225 |